Skip to main content
Sign up for general email updates regarding the ATB
The 2024 Electricity ATB is live! Join the webinar to learn what's new. Register to attend or sign up for general email updates.

Pumped Storage Hydropower

Pumped storage hydropower does not calculate levelized cost of energy (LCOE) or levelized cost of storage (LCOS) and so does not use financial assumptions. Therefore, all parameters are the same for the Research and Development (R&D) and Markets & Policies Financials cases.

2025 Annual Technology Baseline (ATB) data for pumped storage hydropower (PSH) are shown above. Base Year capital costs and resource characteristics are taken from a national closed-loop PSH resource assessment and cost model completed under the U.S. Department of Energy (DOE) HydroWIRES Project D1: Improving Hydropower and PSH Representations in Capacity Expansion Models. Resource assessment assumptions are documented by (Rosenlieb et al., 2022), and subsequent updates are described in (Rosenlieb et al., 2026) and on the National Laboratory of the Rockies's (NLR's) resource data web page Closed-Loop Pumped Storage Hydropower Supply Curves. The cost model used to estimate site-level capital costs is described in (Cohen et al., 2023) with updates in (Rosenlieb et al., 2026). The ATB includes two PSH subtypes: 1) closed-loop systems with two new reservoirs and 2) systems that use one existing reservoir and one new off-river reservoir. Closed-loop systems can use reservoirs built by damming across dry gullies or by constructing ring dams on flat areas. Closed-loop PSH is expected to have reduced impacts on aquatic systems, whereas systems using an existing reservoir can have lower costs (Pracheil et al., 2025). Operations and maintenance (O&M) costs and roundtrip efficiency are based on estimates for a 1,000-megawatt (MW) system reported in the 2020 DOE Grid Energy Storage Technology Cost and Performance Assessment (Mongird et al., 2020). Projected changes in capital costs are based on the DOE Hydropower Vision study (DOE, 2016) and assume different degrees of technology improvement and technological learning. 

The three scenarios for technology innovation are as follows:

  • Conservative Technology Innovation Scenario (Conservative Scenario): no change from baseline capital expenditures (CAPEX) and O&M costs through 2050
  • Moderate Technology Innovation Scenario (Moderate Scenario): no change from baseline CAPEX and O&M costs through 2050, consistent with the Reference case in the DOE Hydropower Vision study (DOE, 2016)
  • Advanced Technology Innovation Scenario (Advanced Scenario): CAPEX reductions of 12% by 2050 based on improved process and design improvements along with advanced manufacturing, new materials, and other technology improvements, consistent with Advanced Technology in the DOE Hydropower Vision study (DOE, 2016); no changes to O&M.

Hydropower technologies are not among the limited set of technologies explored in the pilot Expanded Cost Drivers Case, and therefore 2025 ATB technology innovation scenarios do not capture supply chain constraints or other cost factor assumptions for these technologies.

Resource Categorization

Resource categorization from a national closed-loop PSH resource assessment is described in detail by (Rosenlieb et al., 2022), with subsequent updates described in (Rosenlieb et al., 2026) and on NLR's resource data web page Closed-Loop Pumped Storage Hydropower Supply Curves. Individual sites are identified using geospatial algorithms to delineate potential reservoir boundaries, exclude reservoirs that violate technical potential criteria (e.g., protected land, critical habitat), find all possible reservoir pairings, and then eliminate overlapping reservoirs to produce the least-cost set of nonoverlapping reservoir pairs. Potential reservoirs can be characterized in two ways: 1) earthen embankment dams across dry gully topography and 2) ring-shaped dams on flat topography constructed from roller-compacted concrete. For sites that use existing reservoirs, we include the HydroLAKES dataset of existing reservoirs in the set of total reservoirs used to find reservoir pairings. This procedure is done for alternative storage durations of 8, 10, and 12 hours. Underlying data are site-specific, but for the ATB, resource classes are binned by capital cost so each class contains a roughly equal amount of total national PSH capacity potential. Binning is done at the national level for the data tables below; other representations use region-specific cost bins to better represent the distribution of site characteristics in each region. Physical characteristics and capital cost statistics for each ATB class and a 10-hour storage duration are included in the table below. 

Resource Class Capacity and Capital Costs

ATB ClassTotal Number of Sites IdentifiedTotal Generating Capacity (gigawatts [GW])Site Generating Capacity (MW)Capital Cost
(2021USD/kilowatt [kW])
AverageMinMaxAverageMinMax
 Data for Closed-Loop Sites
Class 18781,0721,2206032,798$2,584$1,909$2,772
Class 29321,0711,1505592,772$2,879$2,772$2,972
Class 31,0081,0721,0634372,128$3,055$2,972$3,131
Class 41,0891,0719843522,734$3,201$3,131$3,270
Class 51,1351,0729443601,796$3,335$3,270$3,400
Class 61,1941,0728983731,775$3,462$3,400$3,522
Class 71,2251,0718743521,864$3,581$3,522$3,642
Class 81,3181,0718133542,619$3,706$3,642$3,766
Class 91,3571,0717893341,715$3,830$3,766$3,893
Class 101,4121,0717593271,715$3,955$3,893$4,014
Class 111,4671,0727302392,281$4,083$4,015$4,145
Class 121,5561,0716892401,621$4,218$4,145$4,288
Class 131,6461,0726512151,623$4,366$4,288$4,445
Class 141,7201,0716232101,883$4,524$4,445$4,603
Class 151,8641,0715751971,509$4,715$4,603$5,308
Totals19,80116,072 
 Data for Sites Requiring One New Reservoir
Class 139661,6917883,589 $1,801$1,508$1,920
Class 244631,4297263,467 $2,016$1,925$2,117
Class 352631,2156132,758 $2,272$2,124$2,431
Class 465639665441,654 $2,604$2,432$2,788
Class 593636813211,443 $3,384$2,789$4,708
Totals293318      

Resource Class Design Values

ATB ClassReservoir Volume (gigaliters)Hydraulic Head (meters [m])Distance Between Reservoirs (m)
AverageMinMaxAverageMinMaxAverageMinMax
 Data for Closed-Loop Sites
Class 18.93.837.85792087334,1168597,483 
Class 28.83.531.45602117304,4691,2077,549
Class 38.43.132.85502187304,4881,2347,693
Class 47.92.528.55482067214,5491,0637,589
Class 57.92.823.15332007324,5721,0257,947
Class 67.52.422.55332007184,6331,2257,471
Class 77.62.829.15192007374,5741,2937,573
Class 87.22.730.95092017394,5209937,508
Class 97.22.521.84962007204,4511,0827,704
Class 107.12.021.24902007214,4609577,681
Class 117.01.726.34792007284,3731,1727,597
Class 126.92.119.84512007194,1499877,464
Class 136.72.321.84372007394,0386007,591
Class 146.71.427.44212007193,9379607,574
Class 156.41.518.33972007183,6938637,515
 Data for Sites Requiring One New Reservoir
Class 114.24.742.54662176792,5671,3135,170
Class 211.55.237.64752306703,2951,3206,567
Class 310.83.929.74122096643,0007386,501
Class 48.34.620.34192056563,5271,3536,975
Class 57.03.115.83242006632,8268636,955

Scenario Descriptions

Cost reductions in the Advanced Scenario reflect various types of technology innovations that could be applied to PSH facilities. These potential innovations, which are discussed in the DOE Hydropower Vision Roadmap (DOE, 2016), are largely similar to technology pathways for hydropower without pumping.

Summary of Technology Innovation: Advanced Scenario

 ModularityNew MaterialsEco-Friendly Pumps and TurbinesInnovative Closed-Loop Concepts
Technology DescriptionDrop-in systems that minimize civil works and maximize ease of manufactureAlternative materials for water diversion (e.g., penstocks)Innovative approaches to improved environmental performanceOff-river designs allowing better combined economic and environmental performance
ImpactsReduced civil works costReduced construction material costsReduced environmental mitigation costsReduced environmental costs and increased modularity and standardization
References(DOE, 2016)(DOE, 2016)(DOE, 2016)(DOE, 2016)

Scenario Assumptions

No explicit deployment assumptions or learning rates are used to define the Advanced Technology Innovation Scenario for PSH. All cost reductions are attributed to improved technology, processes, designs, and contracting along with advanced materials and improved construction practices. Deployed PSH capacity is 23 gigawatts (GW) in the Base Year, and the rate of cost reduction is 0.6%/yr through 2035 and 0.2%/yr from 2035 to 2050. No cost reduction is assumed after 2050.

Representative Technology

The resource assessment procedure requires several design specifications to be defined upfront, and for the PSH capacity included in the ATB, these include hydraulic heads of 200–750 meters (m) for closed-loop sites and 100–750 m for sites using existing reservoirs, a maximum reservoir distance of 12 times the head height, and dam heights of 40, 60, 80, or 100 m for dry gully reservoirs and 15, 20, or 25 m for ring dam reservoirs (Rosenlieb et al., 2022)(Rosenlieb et al., 2026), and Closed-Loop Pumped Storage Hydropower Supply Curves (NLR). Upper and lower reservoir volumes are also assumed to be within 10% of one anther for closed-loop sites with no such restrictions when using existing reservoirs. Given the resulting technical specifications of each reservoir pair, the powerhouse (turbine, generator, and electrical equipment) can be sized flexibly for a given reservoir pair, and here data are included for a powerhouse sized to result in 8, 10, or 12 hours of storage duration (i.e., the maximum number of hours generating at rated capacity). 

Methodology

This section describes the methodology to develop assumptions for CAPEX, operations and maintenance (O&M), and roundtrip efficiency. 

Capital Expenditures (CAPEX)

Capital costs are first calculated for each site using a bottom-up component-level PSH cost model developed at NLR with participation and engagement with hydropower industry stakeholders (Cohen et al., 2023). The cost model uses a detailed set of site specifications for the reservoirs, powerhouse, water conveyance, auxiliary components, and indirect costs to calculate technical specifications and component-level costs that are then aggregated into estimates for total direct and indirect costs for each site. Component costs are estimated largely by using procedures in the Electric Power Research Institute (EPRI) Pumped-Storage Planning and Evaluation Guide (EPRI, 1990) with market adjustment factors to reflect noninflation-based changes in relevant markets since the publication of the EPRI guide. Ring dams made of roller-compacted concrete have lower volume per dam height than earthen dams as described in (Bass, 1991), and cost per unit volume is approximately 12 times that of earthen dams based on data from (Petheram and McMahon, 2019) and the U.S. Army Corps of Engineers National Inventory of Dams ((Rosenlieb et al., 2026)). Grid connection costs are added based on the distance from the powerhouse location (assumed at the lower reservoir) to the nearest high-voltage transmission line node (Maclaurin et al., 2021). One limitation of the capital costs estimated for single reservoir sites is they do not include any additional costs to retrofit an existing facility; instead, they simply exclude one of the reservoir cost components. Thus, single reservoir site costs might be underestimated relative to what might be observed when deploying new PSH at existing reservoirs.

The maps below plot the median CAPEX in each state for each resource class for a PSH subtype when individual sites are binned by cost separately for each state. Some states have zero sites identified, largely because of insufficient elevation differences to meet the minimum head height criteria. The ratio of water conveyance length between reservoirs to head height (L/H ratio) is also shown for individual sites. The display includes links to a bar chart and a tabular display. The bar chart shows more granular data for each balancing area defined in the Regional Energy Deployment System (ReEDS) capacity expansion model along with the state-average PSH capital cost. The table allows the data to be filtered by subtype, class, and balancing area to view region- or class-specific data.

Regional PSH Capital Costs by Class

 

Operation and Maintenance (O&M) Costs

(Mongird et al., 2020) characterize PSH O&M costs using a literature review of recently published sources of PSH cost and performance data. For the 2025 ATB, we use cost estimates for a 1,000-MW plant, which has lower labor costs per power output capacity compared to a smaller facility. O&M costs also include component costs for standard maintenance, refurbishment, and repair. O&M cost reductions are not projected for future years because the relevant technical components are assumed to be mature, so they are constant and identical across all scenarios.

Round-Trip Efficiency

Round-trip efficiency is also based on a literature review by (Mongird et al., 2020), who report a range of 70%–87% across several sources. The value of 80% is taken as a central estimate, and no improvements are projected either in (Mongird et al., 2020) or here because the relevant technical components are assumed to be mature. Thus, roundtrip efficiency is constant and identical across all scenarios. 

References

The following references are specific to this page; for all references in this ATB, see References.

Bass, Randall P. Alternative Dam Construction Techniques. Georgia Institute of Technology, 1991. http://hdl.handle.net/1853/31332.

Cohen, Stuart, Vignesh Ramasamy, and Danny Inman. “A Component-Level Bottom-Up Cost Model for Pumped Storage Hydropower.” National Renewable Energy Laboratory (NREL), Golden, CO (United States), September 19, 2023. https://doi.org/10.2172/2004922.

DOE. “Hydropower Vision: A New Chapter for America’s Renewable Electricity Source.” Washington, D.C.: U.S. Department of Energy, 2016. https://doi.org/10.2172/1502612.

EPRI. “Pumped-Storage Planning and Evaluation Guide.” Palo Alto, CA, January 1990.

Maclaurin, Galen, Nicholas Grue, Anthony Lopez, Donna Heimiller, Michael Rossol, Grant Buster, and Travis Williams. “The Renewable Energy Potential (reV) Model: A Geospatial Platform for Technical Potential and Supply Curve Modeling.” Golden, CO: National Renewable Energy Laboratory, 2021. https://doi.org/10.2172/1563140.

Mongird, Kendall, Vilayanur Viswanathan, Jan Alam, Charlie Vartanian, Vincent Sprenkle, and Richard Baxter. “2020 Grid Energy Storage Technology Cost and Performance Assessment.” Washington, D.C.: U.S. Department of Energy, December 2020. https://www.energy.gov/energy-storage-grand-challenge/downloads/2020-grid-energy-storage-technology-cost-and-performance.

Petheram, C., and T. A. McMahon. “Dams, Dam Costs and Damnable Cost Overruns.” Journal of Hydrology X 3 (April 1, 2019): 100026. https://doi.org/10.1016/j.hydroa.2019.100026.

Pracheil, Brenda M., Kevin P. Duffy, Lin Zeng, and James W. Saulsbury. “Environmental Impacts of Closed-Loop Pumped Storage Hydropower.” Pacific Northwest National Laboratory (PNNL), Richland, WA (United States), January 15, 2025. https://doi.org/10.2172/2500381.

Rosenlieb, Evan, Donna Heimiller, and Stuart Cohen. “Closed-Loop Pumped Storage Hydropower Resource Assessment for the United States.” Golden, CO: National Renewable Energy Laboratory, 2022. https://doi.org/10.2172/1870821.

Rosenlieb, Evan, Victor Igwe, Lindsay Ashworth, Vignesh Ramasamy, and Stuart Cohen. “Methods for Assessing Opportunities for Ring Dam Pumped Storage Hydropower.” Golden, CO: National Laboratory of the Rockies, January 2026. https://docs.nlr.gov/docs/fy26osti/93850.pdf.